Please be advised, there will be 6 monthly UPS testing to Precinct 1 and 2 at St Lucia Campus as per preventative maintenance program attached.
When
- Start: Tuesday 17 May 2022
- Finish: Thursday 9 June 2022
- Times: 6:00am to 3:30pm
Where
- Precinct 3
- Please see program attached for more information
Work details
- UPS static bypass operation check.
- External bypass operation check. (Where exists)
- UPS on-load test as follows. (With load connected to UPS)
- Monitor battery string voltage, if okay continue otherwise check individual cells to determine faulty unit.
- Isolate mains.
- Monitor battery string voltage and record voltage and time.
- Cease test immediately if battery failure detected, otherwise continue to test until battery voltage is at 105% of UPS manufacturers low voltage threshold.
- For multi battery string UPS’s: -
- Isolate one string at a time.
- Measure individual cell voltages.
- Remove external load.
- Measure individual cell voltages.